RCCB — Residual Current Circuit Breaker

Electro-mechanical residual current device that disconnects the protected circuits when earth leakage exceeds the rated value. Neutral on the left.

Approval No.SAA-230476-EA
Certified toAS/NZS 61008.1
Poles1P+N (2 modules) or 3P+N (4 modules)
Rated voltage230/240V AC (1P+N), 400/415V AC (3P+N), 50/60 Hz
Residual current typeType A, Type AC
Rated residual current (IΔn)30 / 100 / 300 / 500 mA (10 mA for 16–32 A 1P+N)
Conditional short-circuit current (Inc)10 kA
Making & breaking (IΔm)500 A (16–50 A), 630 A (63 A)
Tripping time≤ 0.1 s
Electro-mechanical endurance4,000 cycles
Terminal capacityRigid conductor up to 25 mm²
Protection classIP20
Mounting35 mm DIN rail
Order codeRated current (A)
MYLNL26-63L-32C32
MYLNL26-63L-40C40
MYLNL26-63L-50C50
MYLNL26-63L-63C63

Approval SAA-230476-EA (AS/NZS 61008.1), valid until May 2028. An RCCB gives earth-leakage protection only — pair it with circuit breakers for overload and short-circuit protection.

RCCB — Residual Current Circuit Breaker dimensions (mm) — 3p+n and 1p+n
Dimensions (mm) — 3P+N and 1P+N
Download datasheet (PDF) Request full datasheet